    The Fluke 435-II Power Quality and Energy Analyzer is designed to help you minimize downtime, quickly troubleshoot power quality issues and easily discover the costs of wasted energy. Downtime is expensive and getting the data you need to solve to critical power quality problems quickly is key. The 435-II Analyzer measurement process and data output have been optimized to help you access the most critical information easily.
    Multiple parameters are measured simultaneously and displayed in formats that quickly describe overall power quality health. The detailed information helps you make better maintenance decisions—whether you’re trying to reduce energy waste, find the source of power quality issues or see how motor startups are affecting your electrical system. Data can be accessed as simple digital values, trend graphs (for fast insight into changes over time), waveforms, or phasor diagrams. The data can also be analyzed and organized into tabular formats. Detailed event data allows you to see the magnitude, duration and time stamping of anomalies enabling you to rapidly correlate the problems you are experiencing in your facility.
    Specifications: Fluke 434-II and 435-II Power Quality and Energy Analyzers
    Volt
    Model
    Measurement Range
    Resolution
    Accuracy
    Vrms (AC + DC)
    434-II
    1 V to 1000 V phase to neutral
    0.1 V
    ±0.1% of nominal voltage
    1
    435-II
    1 V to 1000 V phase to neutral
    0.01 V
    ±0.1% of nominal voltage
    1
    Vpk
    1 Vpk to 1400 Vpk
    1 V
    5% of nominal voltage
    Voltage Crest Factor (CF)
    1.0 > 2.8
    0.01
    ±5%
    Vrms½
    434-II
    1 V to 1000 V phase to neutral
    0.1 V
    ± 1 % of nominal voltage
    434-II and 435-II
    0.1 V
    ±0.2% of nominal voltage
    Vfund
    434-II
    1 V to 1000 V phase to neutral
    0.1 V
    ± 0.5 % of nominal voltage
    435-II
    0.1 V
    ± 0.1 % of nominal voltage
    Amps (accuracy excluding clamp accuracy)
    Amps (AC + DC)
    i430-Flex 1x
    5 A to 6000 A
    1 A
    ±0.5% ±5 counts
    i430-Flex 10x
    0.5 A to 600 A
    0.1 A
    ±0.5% ±5 counts
    1mV/A 1x
    5 A to 2000 A
    1A
    ±0.5% ±5 counts
    1mV/A 10x
    0.5 A A to 200 A (AC only)
    0.1 A
    ±0.5% ±5 counts
    Apk
    i430-Flex
    8400 Apk
    1 Arms
    ±5%
    1mV/A
    5500 Apk
    1 Arms
    ±5%
    A Crest Factor (CF)
    1 to 10
    0.01
    ±5%
    Amps½
    i430-Flex 1x
    5 A to 6000 A
    1 A
    ±1% ±10 counts
    i430-Flex 10x
    0.5 A to 600 A
    0.1 A
    ±1% ±10 counts
    1mV/A 1x
    5 A to 2000 A
    1 A
    ±1% ±10 counts
    1mV/A 10x
    0.5 A A to 200 A (AC only)
    0.1 A
    ±1% ±10 counts
    Afund
    i430-Flex 1x
    5 A to 6000 A
    1 A
    ±0.5% ±5 counts
    i430-Flex 10x
    0.5 A to 600 A
    0.1 A
    ±0.5% ±5 counts
    1mV/A 1x
    5 A to 2000 A
    1 A
    ±0.5% ±5 counts
    1mV/A 10x
    0.5 A A to 200 A (AC only)
    0.1 A
    ±0.5% ±5 counts
    Hz
    Hz
    Fluke 435 @ 50 Hz Nominal
    42.500 Hz to 57.500 Hz
    0.001 Hz
    ±0.01 Hz
    Fluke 435 @ 60 Hz Nominal
    51.00 Hz to 69.00 Hz
    0.001 Hz
    ±0.01 Hz
    Power
    Watts (VA, var)
    i430-Flex
    max 6000 MW
    0.1 W to 1 MW
    ±1% ±10 counts
    1 mV/A
    max 2000 MW
    0.1 W to 1 MW
    ±1% ±10 counts
    Power Factor (Cos j/DPF)
    0 to 1
    0.001
    ±0.1% @ nominal load conditions
    Energy
    kWh (kVAh, kvarh)
    i430-Flex 10x
    Depends on clamp scaling and V nominal
    ±1% ±10 counts
    Energy Loss
    i430-Flex 10x
    Depends on clamp scaling and V nominal
    ±1% ±10 counts Excluding line resistance accuracy
    Harmonics
    Harmonic Order (n)
    DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7
    Inter-Harmonic Order (n)
    OFF, 1 to 50 Grouping: Harmonic and Interharmonic subgroups according to IEC 61000-4-7
    Volts %
    f
    0.0% to 100%
    0.1%
    ±0.1% ±n x 0.1%
    r
    0.0% to 100%
    0.1%
    ±0.1% ±n x 0.4%
    Absolute
    0.0 to 1000 V
    0.1 V
    ±5%
    1
    THD
    0.0% to 100%
    0.1%
    ±2.5%
    Amps %
    f
    0.0% to 100%
    0.1%
    ±0.1% ±n x 0.1%
    r
    0.0% to 100%
    0.1%
    ±0.1% ±n x 0.4%
    Absolute
    0.0 to 600 A
    0.1 A
    ±5% ±5 counts
    THD
    0.0% to 100%
    0.1%
    ±2.5%
    Watts %
    f or r
    0.0% to 100%
    0.1%
    ±n x 2%
    Absolute
    Depends on clamp scaling and V nominal

    ±5% ±n x 2% ±10 counts
    THD
    0.0% to 100%
    0.1%
    ±5%
    Phase Angle
    -360° to +0°

    ±n x 1°
    Flicker
    Plt, Pst, Pst (1 min) Pinst
    0.00 to 20.00
    0.01
    ±5%
    Unbalance
    Volts %
    0.0% to 20.0%
    0.1%
    ±0.1%
    Amps %
    0.0% to 20.0%
    0.1%
    ±1%
    Mains Signaling
    Threshold Levels
    Threshold, limits and signaling duration is programable for two signaling frequencies


    Signaling Frequency
    60 Hz to 3000 Hz
    0.1 Hz
    Relative V %
    0% to 100%
    0.10%
    ±0.4%
    Absolute V3s (3 second avg.)
    0.0 V to 1000 V
    0.1 V
    ±5% of nominal voltage
    General Specifications
    Case
    Design Rugged, shock proof with integrated protective holster Drip and dust proof IP51 according to IEC60529 when used in tilt stand position Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g 2 /Hz according to MIL-PRF-28800F Class 2
    Display
    Brightness: 200 cd/m 2 typ. using power adapter, 90 cd/m 2 typical using battery power Size: 127 x 88 mm (153 mm/6.0 in diagonal) LCD Resolution: 320 x 240 pixels Contrast and brightness: user-adjustable, temperature compensated
    Memory
    8GB SD card (SDHC compliant, FAT32 formatted), up to 32GB optionally. Screen save and multiple data memories for storing data including recordings (dependent on memory size).
    Real-Time Clock
    Time and date stamp for Trend mode, Transient display, System Monitor and event capture
    Environmental
    Operating Temperature
    0°C ~ +40°C; +40°C ~ +50°C excl. battery
    Storage Temperature
    -20°C ~ +60°C
    Humidity
    +10°C ~ +30°C: 95% RH non-condensing
    +30°C ~ +40°C: 75% RH non-condensing
    +40°C ~ +50°C: 45% RH non-condensing
    Maximum Operating Altitude
    Up to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V
    Up to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V
    Maximum storage altitude 12 km (40,000 ft)
    Electro-Magnetic-Compatibility (EMC)
    EN 61326 (2005-12) for emission and immunity
    Interfaces
    Mini-USB-B, Isolated USB port for PC connectivity SD card slot accessible behind instrument battery